Approximate Full Load Direct Motor Amperes
 
3 Phase KVA = Volts x Amps x 1.73
1000
 
Horsepower 90V 120V 180V 240V 500V 550V
1/4 4.0 3.1 2.0 1.6 ----- -----
1/3 5.2 4.1 2.6 2.0 ----- -----
1/2 6.8 5.4 3.4 2.7 ----- -----
3/4 9.6 7.6 4.8 3.8 ----- -----
1 12.2 9.5 6.1 4.7 ----- -----
1-1/2 ----- 13.2 8.3 6.6 ----- -----
2 ----- 17.0 10.8 8.5 ----- -----
3 ----- 25.0 16.0 12.2 ----- -----
5 ----- 40.0 27.0 20.0 ----- -----
7-1/2 ----- 58.0 ----- 29.0 13.6 12.2
10 ----- 76.0 ----- 38.0 18.0 16.0
15 ----- ----- ----- 55.0 27.0 24.0
20 ----- ----- ----- 72.0 34.0 31.0
25 ----- ----- ----- 89.0 43.0 38.0
30 ----- ----- ----- 106.0 51.0 46.0
50 ----- ----- ----- 173.0 83.0 75.0
75 ----- ----- ----- 255.0 123.0 111.0
100 ----- ----- ----- 341.0 164.0 148.0
Note: If motors are started more than once per hour add 20% additional KVA.